Apc Smart-Ups SRT10000VA 10kva 230v
APC Smart-UPS SRT 10000VA 230V
-
10/100 BaseT ConnectionConnect the device to a network using a 10 or 100 BaseT connection
-
Battery failure notificationProvides early-warning fault analysis on batteries enabling timely preventive maintenance
-
Green modeThe patent-pending operating mode bypasses unused electrical components in good power conditions to achieve very high operating efficiency without sacrificing any protection.
-
LCD graphics displayText and mimic diagrams that display modes of operation, system parameters, and alarms.
Smart-UPS On-Line Features & Benefits
Serviceability
-
Audible alarmsProvides notification of changing utility power and UPS power conditions
-
Predictive failure notificationProvides early-warning fault analysis ensuring proactive component replacement.
-
Disconnected battery notificationWarns when a battery is not available to provide backup power.
-
User-replaceable batteriesIncreases availability by allowing a trained user to perform upgrades and replacements of the batteries reducing Mean Time to Repair (MTTR)
-
Automatic self-testPeriodic battery self-test ensures early detection of a battery that needs to be replaced.
Adaptability
-
Plug-and-Play external batteriesEnsures clean, uninterrupted power to the loads when adding extra runtime to the UPS.
-
Rack/Tower convertibleProtects the initial investment in the UPS when migrating from tower to rack-mount environment.
-
Flash upgradeable firmwareInstall maintenance releases of firmware remotely using FTP.
Manageability
-
LED status indicatorsQuickly understand unit and power status with visual indicators.
-
Serial connectivityProvides management of the UPS via a serial port.
-
Network manageableProvides remote power management of the UPS over the network.
-
InfraStruXure Manager CompatibleEnables centralized management via the APC InfraStruXure Manager.
-
SmartSlotCustomize UPS capabilities with management cards.
Protection
-
Frequency and voltage regulationGives higher application availability by correcting poor frequency and voltage conditions without using the battery.
-
Power conditioningProtects connected loads from surges, spikes, lightning, and other power disturbances.
-
Input power factor correctionMinimizes installation costs by enabling the use of smaller generators and cabling.
-
Generator compatibleEnsures clean, uninterrupted power to protected equipment when generator power is used.
-
Cold-start capableProvides temporary battery power when the utility power is out.
-
Resettable circuit breakerEasy recovery from overloads; no need to replace a fuse.
-
Safety-agency approvedEnsures the product has been tested and approved to work safely with the connected service provider equipment and within the specified environment.
Availability
-
Scalable runtimeAllows additional run time to be quickly added as needed.
-
Intelligent battery managementMaximizes battery performance, life, and reliability through intelligent, precision charging.
-
Hot-swappable batteriesEnsures clean, uninterrupted power to protected equipment while batteries are being replaced
-
Automatic restart of loads after UPS shutdownAutomatically starts up the connected equipment upon the return of utility power.
-
Temperature-compensated battery chargingProlongs battery life by regulating the charge voltage according to battery temperature.
-
Automatic internal bypassSupplies utility power to the connected loads in the event of a UPS power overload or fault.
Marketing Features
-
Low operating and maintenance costs with proven reliability and intelligent battery management.Intelligent battery management, pioneered by APC, maximizes battery performance and life through intelligent, precision temperature-compensated charging. Automatic self-tests insure battery reliability and warn customers in advance of battery replacement. Convenient, easy-to-connect, hot-swappable battery modules provide battery replacement without powering down.
-
Save time with easy and convenient remote/network accessibility.Network manageable via serial, USB, or Ethernet. Includes Powerchute® Software for convenient monitoring and control, safe operating system shutdown, and innovative energy management capabilities.
-
Peace of mind that comes with full equipment compatibility and reliability of a leaderProvides pure sine wave output which is recommended by server manufacturers using active power factor corrected (PFC) power supplies. Safety agency tested and approved means that you can deploy Smart-UPS with confidence that they meet or exceed the industry’s most rigorous standards.
-
Avoids costly power problems by keeping your IT equipment and data protected and available.
Output
-
Output power capacity
10.0 KWatts / 10.0 kVA
-
Max Configurable Power (Watts)
10.0 KWatts / 10.0 kVA
-
Nominal Output Voltage
230V
-
Output Voltage Distortion
Less than 2%
-
Output Frequency (sync to mains)
50/60Hz +/- 3 Hz
-
Other Output Voltages
220, 240
-
Load Crest Factor
3: 1
-
Topology
Double Conversion Online
-
Waveform type
Sine wave
-
Output Connections(6) IEC 320 C13 (Battery Backup)(4) IEC 320 C19 (Battery Backup)(1) Hard Wire 3-wire (H N + G) (Battery Backup)(3) IEC Jumpers (Battery Backup)
-
Bypass
Internal Bypass (Automatic and Manual)
Input
-
Nominal Input Voltage
230V , 400V 3PH
-
Input frequency
40 – 70 Hz (auto sensing)
-
Input Connections
Hard Wire 3 wire (1PH+N+G), Hard Wire 5-wire (3PH + N + G)
-
Input voltage range for main operations
160 – 275V
-
Input voltage adjustable range for mains operation
100 – 275 (half load), 173 – 476 (half load)V
-
Other Input Voltages
220, 240, 380, 415
Batteries & Runtime
-
Battery type
Maintenance-free sealed Lead-Acid battery with suspended electrolyte: leakproof
-
Typical recharge time
1.5hour(s)
-
Nominal Battery Voltage
+/-192 V (split battery referenced to neutral)
-
Replacement Battery
APCRBC140
-
Expected Battery Life (years)
3 – 5
-
RBC Quantity
2
-
Extendable Run Time
1
-
Extended Run Options
APC-Smart-UPS-SRT-10000VA-230V
-
RuntimeView Runtime Chart
-
Efficiency
Communications & Management
-
Interface Port(s)
RJ-45 10/100 Base-T , RJ-45 Serial , Smart-Slot , USB
-
Control panel
Multi-function LCD status and control console
-
Audible Alarm
Audible and visible alarms prioritized by severity
-
Emergency Power Off (EPO)
Yes
-
Available SmartSlot™ Interface Quantity
1
Surge Protection and Filtering
-
Surge energy rating
480Joules
Physical
-
Maximum Height
432mm, 43.2CM
-
Maximum Width
263mm, 26.3CM
-
Maximum Depth
715mm, 71.5CM
-
Net Weight
111.82KG
-
Shipping weight
126.82KG
-
Shipping Height
461mm, 46.1CM
-
Shipping Width
600mm, 60.0CM
-
Shipping Depth
1000mm, 100.0CM
-
Color
Black
Environmental
-
Operating Temperature
0 – 40 °C
-
Operating Relative Humidity
0 – 95 %
-
Operating Elevation
0-3000meters
-
Storage Temperature
-15 – 45 °C
-
Storage Relative Humidity
0 – 95% non-condensing %
-
Storage Elevation
0-15000meters
-
Audible noise at 1 meter from the surface of the unit
55.0dBA
-
Online thermal dissipation
1947.0BTU/hr
-
Protection Class
IP 20
Conformance
-
Approvals
CE, CE Mark, EAC, EN/IEC 62040-1, EN/IEC 62040-2, IRAM, RCM, VDE
-
Standard warranty
3 years for repair or replacement (excluding battery) and 2 years for battery
Sustainable Offer Status
-
RoHS
Compliant
-
REACH
REACH: Contains No SVHCs
-
Battery Directive
Compliant
Reviews
There are no reviews yet.